GSD7666-WJH is an advanced single-phase two wire energy meter with basic measurement function for residential customersin postpayment mode. The meter has outstanding function of detecting & preventing power tampering like bypassing.
Main Features
·Screw sealing
·Push button
·Real-time clock
·Infrared port (optional)
·Detection & prevention of tampering
·Active energy measurement
·Import & export energy measurement
·Neutral current measurement
·Programmable auto-scroll display
·LCD display capable of reading without power
·Extended transparent terminal cover
Dimension
ELECTRICAL PARAMETERS
VOLTAGE |
Nominal voltage Un |
230V |
Limited voltage |
70% ~ 120%Un |
FREQUENCY |
Nominal frequency fn |
50 ~ 60Hz |
Tolerance |
±5% |
CURRENT |
Basic current(Ib) |
5A |
Maximum current(Imax) |
60A (80A/100A optional)
|
Starting current(Ist) |
20mA |
Active energy constant |
1000imp/kWh |
MEASUREMENTACCURACY |
Active energy as IEC62053-21 |
Class 1.0 |
POWERCONSUMPTION |
Voltage circuit |
<2W<8VA |
Current circuit |
<1VA |
TEMPERATURE RANGE |
Operation range |
-25℃ ~ +70℃ |
Storage range |
-40℃ ~ +85℃ |
INSULATION
Insulation level |
4kV rms 1min |
Impulse withstand voltage |
8kV 1.2/50 μs |
Insulation system classification |
Protection class II |
ELECTRO MAGNETIC COMPATIBILITY
ELECTROSTATIC DISCHARGES |
Contact discharge |
8kV |
Air discharge |
15kV |
ELECTROMAGNETIC RF FIELDS |
27MHz to 500MHz typical |
10V/m |
100kHz to 1GHz typical |
30V/m |
Fast transient burst test |
4kV |
MECHANICAL REQUIREMENTS |
Meter case protection class |
IP54 |
Insulation system classification |
Protection class II |
Maximum cable size |