GST7666-CT1 is a CT(current transformer)-connection three- phase multi-function energy meter with modular design. The meter is ideal for large residential homes and small commercial & industrial c
GST7666-CT1 is a CT(current transformer)-connection three- phase multi-function energy meter with modular design. The meter is ideal for large residential homes and small commercial & industrial customers, with exchangeable communication modules supporting PLC or RF and complying with DLMS communication protocol. The built-in tariff structure supports measurement of active energy, reactive energy & apparent energy
Main Features
·Multi-tariff ·AMI-system integrated ·DLMS/COSEM compliant ·Infrared port/RS485 ·20-digit STS encryption ·Tamper detection & recording |
·Import & export energy measurement ·LCD display capable of reading without power ·Disconnecting on overload & no-credit condition ·Programmable warning of power limit & low credit ·Dual power source switchable between power grid & solar system ·Maximum demand measurement & load profiling (customizable) |
Split-type Structure for Anti-tampering Protection
The meter consists of two parts, the MCU (Metering & Control Unit) and CIU (Customer Interface Unit), which could be linked via communication modes of M-bus, PLC or RF based on requirements.The CIU is installed inside the customer’s home for inputting prepayment token and searching for information, while the MCU is normally installed in a meter enclosure away from the customer’s home.
ELECTRICAL PARAMETERS
VOLTAGE/FREQUENCY/CURRENT | |
Nominal voltage Un | 3x230/240V |
Limited voltage | 60% ~ 120%Un |
Frequency | 50/60Hz±5% |
Basic current(Ib) | 1.5A |
Maximum current(Imax) | 6A |
Starting current(Ist) | 30mA |
Active energy constant | 6400imp/kWh |
Reactive energy constant
|
6400imp/kvarh
|
ACCURACY | |
Active energy as IEC62053-21 | Class 1.0 |
Reactive energy as IEC62053-23 | Class 2.0 |
POWERCONSUMPTION | |
Voltage circuit | <2W <8VA |
Current circuit | <1VA |
TEMPERATURERANGE | |
Operation range | -25℃ ~ +70℃ |
Storage range | -40℃ ~ +85℃ |
INSULATION
Insulation level | 4kV rms 1min |
Impulse withstand voltage | 8kV 1.2/50 μs |
ELECTRO MAGNETIC COMPATIBILITY
ELECTROSTATIC DISCHARGES | |
Contact discharge | 8kV |
Air discharge | 15kV |
ELECTROMAGNETIC RF FIELDS | |
27MHz to 500MHz typical | 10V/m |
100kHz to 1GHz typical | 30V/m |
Fast transient burst test | 4kV |
MECHANICAL REQUIREMENTS | |
Meter case protection class | IP54 |
Insulation system classification | Protection class II |
Maximum cable size | 10 mm |